FSDR-511
Combination Fire Smoke Damper
Application
Round Steel Blade
Model FSDR-511 is a combination fire smoke damper with round style
blades. The FSDR-511 has been qualified to 3000 fpm (15.2 m/s) and
4 in. wg (1 kPa) for operation and dynamic closure in emergency fire
smoke situations. Model FSDR-511 may be installed vertically (with
blades running horizontal) or horizontally and is rated for airflow and
leakage in either direction.
UL 555S Leakage Class I
UL555 1 1/2 Hour Fire Resistance Rating
Model FSDR-511 meets the requirements for fire
dampers, smoke dampers and combination fire
smoke dampers established by:
Ratings
UL 555 Fire Resistance Rating
Fire Rating: 1 1/2 Hour
National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B, 101, & 105
IBC International Building Codes
New York City (MEA listing #260-91-M)
California State Fire Marshall
Dynamic Closure Rating: Actual ratings are size dependant
Maximum Velocity: 3000 fpm (15.2 m/s)
Maximum Pressure: 4 in. wg (1 kPa)
UL 555S Leakage Rating
Leakage Class:
I
Listing #: 3225-0981:112 (fire)
Operational Rating: Actual ratings are actuator dependant
Maximum Velocity: 3000 fpm (15.2 m/s)
Listing #: 3230-0981:113 (smoke)
Maximum Pressure: 4 in. wg (1 kPa)
Maximum Temperature: 350º F (177°C) —Depending on actuator
“UL CLASSIFIED (see complete marking on
product)”
Standard Construction
“UL CLASSIFIED to Canadian safety standards
(see complete marking on product)”
Standard 555 (Listing #R13317)
Frame/Sleeve: 20 ga. (1mm) galvanized steel round
Blade: Double skin galvanized steel (14 ga.
[2mm] equivalent) round style blades
Standard 555S (Listing #R13447)
Seal: Extruded silicone rubber blade seals
Axle: 1/2 in. (13mm) dia. plated steel
Bearings: Stainless steel sleeve type
Fusible Link: UL listed 165ºF (74ºC) -not 304SS
Size Limitations
Minimum Size: 6 in. (152mm) diameter
Maximum Size: 24 in. (610mm) diameter
Optional Features
• OCI (Open closed indication switches)
• 165º F (74°C), 212º F (100°C), and 350º F (177°C) RRL available
• TOR (remote override of 165º F (74°C) closure allows damper to
perform smoke management functions during a fire emergency)
• Electric or pneumatic actuators to accomplish smoke management
and system functions.
• One retainer plate required, additional retainer plate available.
• 14 ga. (2mm) or 16 ga. (1.5mm) frame/sleeve
* Dimensions furnished approximately 1/8 in. (3mm) undersize.
Opening + 2 in. Min.
Nut
Clamping
Minimum Wall/Floor Opening
Screw
Retaining
Plate Assembly
= Nominal Dia. + 7/8 in.
1.00 in. Min. Typ.
Fasteners
Clamping Screw
|
Grandstream Networks Telephone HANDYTONE 286 User Manual
Grundig Automobile Accessories VCH 3610 User Manual
Grundig DVR 5550 HDD User Manual
Harbor Freight Tools Saw 41146 User Manual
Heath Zenith Home Safety Product SH 5408 User Manual
Hotpoint Microwave Oven AHP67X User Manual
Hotpoint Refrigerator 6936 User Manual
HP Hewlett Packard Welder 53A User Manual
Humax Flat Panel Television LGB 19DRT User Manual
Hunter Fan Outdoor Ceiling Fan 21337 User Manual